  • ✔︎ Class 1, 2 or 3 oil igniter
    Capacity range from 6 to 30 MBtu/hr.

    ✔︎ Application Flexibility
    The protected primary combustion zone ensures reliable operation in multiple environments.

    ✔︎ Easy Retrofit
    With a diameter of only 4″, the DURAFire® fits most burners.

    ✔︎ Low Maintenance Requirements
    No moving parts, a self-cleaning spark tip and no tools required to perform periodic inspection.

    ✔︎ Reliable Ignition
    95% ignition rate in most applications.

    ✔︎ High Efficiency Air Atomizer
    The internal mix atomizer is selected from a standard set of sizes for each project.

    ✔︎ Cooling/Combustion Air
    Low cooling/combustion air requirements.

    ✔︎ Durability
    Heavy duty material and no moving parts to wear out.

    ✔︎ Compatibility
    Fits most existing mount tubes minimizing retrofit installation costs.

  • ➤ Fuel → No. 2 oil

    ➤ Capacity Rating* → 6-33 MBtu/hr (1.76-9.67 MW)

    ➤ Atomization Media → Air

    ➤ Fuel Pressure → 60 psig (4.22 kg/cm2) at igniter

    ➤ Atomizing Air → Pressure: 80 psig (5.62 kg/cm2) at igniter

    ➤ Flow → 0.40 lb air/1 lb fuel

    ➤ Cooling / Combustion Air → Flow: 60 SCFM (at igniter)

    ➤ Pressure Drop → Approximately 3 in. (76.2mm ) WC across device

    ➤ Connection → 1½ inch NPT female

    ➤ Length → Available in 2 inch (50.8mm) increments from 24 to 180 inches (609 to 4572 mm)

    ➤ Guide Tube Outside Diameter → 4”(101.6 mm) – igniter can be installed in an existing mount tube for a 4” (101.6 mm) diameter device

    ➤ Mount Tube Outside Diameter → 4.5” (114.3 mm)

    ➤ Construction Material → Guide Tube and Mount Tube – Carbon Steel, Furnace End of Guide Tube -304 Stainless Steel, Oil Tip Assembly – 304 Stainless Steel

    ➤ Retraction Assembly → Per Customer Requirements

    ➤ Oil Tip Assembly → Narrow or Wide angle, as required

    ➤ NFPA → Class 1, 2 or 3

    ➤ Input Voltage → 120 to 240 VAC, 50/60 Hz

    ➤ Input Power → 120 VAC @ 1.5 A (2-A fuse); 240 VAC @ 0.75A (1-A fuse)

    ➤ Output Voltage → 2000 VDC

    ➤ Output Energy → 12 joules per spark

    ➤ Spark Rate: → 3 per second (approximately)